Communication
6.2.4 Information mapping table
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
46
Power Parameters
Phase B reactive power 1012 H signed int 2 bytes R -32767...32767 1 var
Phase C reactive power 1013 H signed int 2 bytes R -32767...32767 1 var
Total reactive power 1014 H signed int 2 bytes R -32767...32767 1 var
Phase A apparent
power
1015 H
signed int
2 bytes R -32767...32767
1 VA
Phase B apparent
power
1016 H
signed int
2 bytes R -32767...32767
1 VA
Phase C apparent
power
1017 H
signed int
2 bytes R -32767...32767
1 VA
Total apparent power 1018 H signed int 2 bytes R -32767...32767 1 VA
Phase A power factor 1019 H signed int 2 bytes R -1000...1000 0.001
Phase B power factor 101A H signed int 2 bytes R -1000...1000 0.001
Phase C power factor 101B H signed int 2 bytes R -1000...1000 0.001
Total power factor 101C H signed int 2 bytes R -1000...1000 0.001
Frequency 101D H unsigned int 2 bytes R 0...65535 0.01 Hz
Phase A angle 1023 H unsigned int 2 bytes R 0...3600 0.1
Phase B angle 1024 H unsigned int 2 bytes R 0...3600 0.1
Phase C angle 1025 H unsigned int 2 bytes R 0...3600 0.1
Parameter Address Data Type Length R/W Data Range Unit
Parameter Address Data Type Length R/W Data Range Unit
Phase A import active
power high 16 bits
2000 H
unsigned
long
4 bytes R 0...4294967295 0.1 Wh
Phase A import active
power low 16 bits
2001 H
Phase B import active
power high 16 bits
2002 H
unsigned
long
4 bytes R 0...4294967295 0.1 Wh
Phase B import active
power low 16 bits
2003 H
Phase C import active
power high 16 bits
2004 H
unsigned
long
4 bytes R 0...4294967295 0.1 Wh
Phase C import active
power low 16 bits
2005 H
Total import active
power high 16 bits
2006 H
unsigned
long
4 bytes R 0...4294967295 0.1 Wh
Total import active
power low 16 bits
2007 H
Phase A import reactive
power high 16 bits
2008 H
unsigned
long
4 bytes R 0...4294967295 0.1 varh
Phase A import reactive
power low 16 bits
2009 H
Phase B import reactive
power high 16 bits
200A H
unsigned
long
4 bytes R 0...4294967295 0.1 varh
Phase B import reactive
power low 16 bits
200B H
Phase C import reactive
power high 16 bits
200C H
unsigned
long
4 bytes R 0...4294967295 0.1 varh
Phase C import reactive
power low 16 bits
200D H