Communication
6.2.4 Information mapping table
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
50
Note
High bytes BIT0 to BIT3 respectively mean status of binary input 1 to 4. Bit value 0 means input is open while
1 means input is closed.
Low bytes BIT0 and BIT1 respectively mean status of relay output 1 and 2. Bit value 0 means contact is open
(relay no operation) while 1 means contact is closed (relay closed).
Other Parameters
Parameter Address Data Type Length R/W
Data
Range
Remark
Demand interval 0130 H unsigned int 2 bytes R/W 1 ... 60 Unit: min.
Sliding window
time
0131 H unsigned int 2 bytes R/W
1 ... 60 Unit: min.
Voltage specifica-
tion
0134 H unsigned int 2 bytes R/W 0 ... 3
3-phase-3-wire 0: 100 V;
3: 380 V;
3-phase-4-wire 1: 220 V;
2: 57.7 V;
Cyclic display time 0132 H unsigned int 2 bytes R/W 1 ... 99 Unit: sec
Number of cyclic
display items
0133 H unsigned int 2 bytes R/W 00 ... FF
1
st
screen of cyclic
display item of
screen A
0140 H unsigned int 2 bytes R/W 0 ... 999
See cyclic display code
table of area A
Number n screen
of cyclic display
item of screen A
... unsigned int 2 bytes R/W 0 ... 999
16
th
screen of
cyclic display item
of screen A
014F H unsigned int 2 bytes R/W 0 ... 999
1
st
screen of cyclic
display item of
screen B
0150 H unsigned int 2 bytes R/W 0 ... 999
See cyclic display code
table of area B
Number n screen
of cyclic display
item of screen B
... unsigned int 2 bytes R/W 0 ... 999
16
th
screen of
cyclic display item
of screen B
015F H unsigned int 2 bytes R/W 0 ... 999