Communication
6.2.4 Information mapping table
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
65
Note
X-0 means maximum value while X=1 means minimum value.
This manual applies to software version for 150910 and later released by the device.
■
Phase A apparent
power
701D H signed int 2 bytes R -32767 ... 32767 1 VA
Phase B apparent
power
701E H signed int 2 bytes R -32767 ... 32767 1 VA
Phase C apparent
power
701F H signed int 2 bytes R -32767 ... 32767 1 VA
Total apparent power 7020 H signed int 2 bytes R -32767 ... 32767 1 VA
Phase A power factor 7021 H signed int 2 bytes R -1000 ... 1000 0.001
Phase B power factor 7022 H signed int 2 bytes R -1000 ... 1000 0.001
Phase C power factor 7023 H signed int 2 bytes R -1000 ... 1000 0.001
Total power factor 7024 H signed int 2 bytes R -1000 ... 1000 0.001
Frequency 7025 H unsigned int 2 bytes R 0 ... 65535 0.01 Hz
Phase A import reac-
tive power high 16 bits
7026 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 varh
Phase A import reac-
tive power low 16 bits
7027 H
Phase B import reac-
tive power high 16 bits
7028 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 varh
Phase B import reac-
tive power low 16 bits
7029 H
Phase C import reac-
tive power high 16 bits
702A H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 varh
Phase C import reac-
tive power low 16 bits
702B H
Total import reactive
power high 16 bits
702C H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 varh
Total import reactive
power low 16 bits
702D H
Voltage unbalance rate 702E H unsigned int 2 bytes R 0 ... 65535 0.01%
Current unbalance rate 702F H unsigned int 2 bytes R 0 ... 65535 0.01%
Binary inputs 7030 H unsigned int 2 bytes R
High byte: bit 0 to bit 3
express input 1 to input 4
status
Low byte: bit 0 to bit 1
express output 1 to output
2 status
Parameter Address Data Type Length R/W Data Range Unit