7 Operation at Use of a PC
7.3 Configuration of the Device
132 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
7.3.3.2 Automation Functions
7.3.3.2.1 Limit Settings
In the Select automation functions menu you can set upper or lower limits for up to 16 measured values. Limit
violations of the upper or lower value range can be output as indications. Up to 4 limiting value violations can
be signaled at the device via the two binary outputs and the LEDs H1 and H2. Furthermore, all 16 limit violations
can be sent to peripheral devices via Ethernet.
The programmable limits are divided into two groups Measurand limits 1-8 and Measurand limits 9-16. The
parameterization is identical for all limits.
Default Settings and Setting Ranges of the Limits
Table 7-6 Limit Settings
Parameter Default Setting Setting Range
Measurand -none- Acc. to list box
(see Operating Parameters)
Limit 0.0 -1 000 000 000 to 1 000 000 000 (unit)
Limit type Lower Lower
Upper
Hysteresis (%) 1.0 0.0 to 10.0
Violation indication Limit Violation x
(x = 1 to 16)
The name of the limit violation indication is
customizable.