7 Operation at Use of a PC
7.3 Configuration of the Device
133SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Parameterizing a Limit
To change, for example, limit 1, proceed as follows:
✧ In the navigation window, select the Operational menu, then the Select automation functions submenu
and click Measurand limits 1-8.
Figure 7-33 Configure Tab, Measurand Limits 1-8 Input/Output Window (Detail)
✧ Enter the desired values in the fields and select the parameters in the list boxes and option fields as
described in Table 7-6.
Hysteresis of the Limit Value Violation
Figure 7-34 Hysteresis (General Representation)
t
100 %
0 %
Start StartEnd End
Permissible
range
Limit Min
Limit Max
Hysteresis range
NOTE
Select Measurand -none- to disable the corresponding measurand limit indication.