7 Operation at Use of a PC
7.3 Configuration of the Device
146 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
1)
The created PQDIF files can be downloaded via the User Interface or with the IEC 61850 protocol.
2)
The created CSV files can be downloaded via the User Interface.
3)
The trend recorder also creates a PQDIF file when 1024 data points (voltage values with a time stamp)
have been generated within the recording interval.
Recorder of average - Max no no
yes
Harmonics parity Odd Even
Odd
All
File generation every
(corresponds to the setting of
the Average interval parame-
ter)
24 h File generation
every:
At average interval
1 h 30 s
2 h 1 min
2 h 10 min, 15 min,
30 min, 1 h or
2 h
4 h
6 h
12 h
24 h
Recorded file type PQDIF PQDIF
1)
(see chapter 7.4.2.4)
CSV
2)
All
Flicker lamp model 230 V 230 V
120 V
Trend Recorder
Tolerance unit Percentage Percentage
Numerical
Tolerance number Percentage: 3 % of declared
input voltage Udin,
Numerical: 0.50 V
1% to 5% in 1 % steps
0.2 V to 500.0 V
Maximum recording interval 10 min 10 min, 30 min, 1 h, 2 h, 4 h, 6 h,
12 h, 24 h
3)
Table 7-13 Recorder Management (SICAM P855) (cont.)