7 Operation at Use of a PC
7.3 Configuration of the Device
147SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
To change the Recorder management, proceed as follows:
In the navigation window, select the Recording and Reporting menu and click Recorder management.
Figure 7-42 Configure Tab, Recorder Management Input/Output Window
Select the desired parameters in the list boxes and option fields as described in Table 7-12.
After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
If you do not want to make any additional settings, continue with the Activation of the device configuration
according to section Activating the Set of Parameters. If you want to change other settings, enter the
changes and then enable the device configuration as described in section Activating the Set of
Parameters.
NOTE
The voltage is recorded in the following connection types:
in the connection type 3P4W (3 phases/4 wires): phase-to-phase voltage or
phase-to-ground voltage
in the connection type 3P3W (3 phases/3 wires): only phase-to-phase voltage
NOTE
Siemens recommends selecting the PQDIF setting from the Recorded file type list box. When selecting All or
CSV, the internal memory will be full prematurely if the CSV file becomes very large compared to the PQDIF file.