7 Operation at Use of a PC
7.3 Configuration of the Device
152 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
To change the memory management, proceed as follows:
In the navigation window, select the Recording and Reporting menu and click Memory management.
Figure 7-45 Configure Tab, Storage Input/Output Window
Select the respective parameters in the list boxes according to Table 7-15 and enter the desired values in
the associated fields.
After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
If you do not want to make any additional settings, continue with the Activation of the device configuration
according to section Activating the Set of Parameters. If you want to change other settings, enter the
changes and then enable the device configuration as described in section Activating the Set of
Parameters.
NOTE
When the device has been recording data for a longer period already, a modification of the memory areas might
lead to the following message:
Memory size should not be changed now. If you active changes, all PQ data will be lost. Please backup data
before activation or cancel changes.
This message is only output if the stored data and the data to be expected exceed the storage capacity of the
SD card.
NOTE
The example is for SICAM P855, for SICAM P850, only has measurement recorder and fault recorder.