7 Operation at Use of a PC
7.6 Example of a Parameterization and Measured Value Evaluation for SICAM P855
210 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
On the Configure tab, Memory management menu item (see Memory Management) allocate 50 % of
the storage capacity to the Measurement recorder.
Figure 7-91 Configure Tab, Memory Management Example
Confirm the factory-set report configuration (see Report Configuration (Only SICAM P855)).
On the Configure tab, Recording control menu item (see Recording Parameters and Power Quality
Data) select Start immediately.
Figure 7-92 Configure Tab, Start Immediately Example
Go to the Configure tab, Save configuration to file menu item to save your device configuration as the
active parameter set as described in Save Configuration to File.
Enable the active parameter set in the device as described in Activating the Set of Parameters.
NOTE
After changing the network settings and subsequent parameter activation the device will reset.