10 Calibration
10.4 Calibrating the Measuring Voltage Input of Neutral Conductor VN
249SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Click the AC Calibration element in the navigation window.
Figure 10-9 Calibrating the Neutral Voltage in the Neutral Conductor
Check which measuring range is presently used in the input/output window at
Actual measuring range is: 63.5 V / 1 A.
Enter the maintenance password into the Password field.
Enter the reference voltage 63.5 V that is generated by the measurement setup into the Neutral voltage
field.
Click Calibrate neutral.
The device executes the calibration and the lower field of the input/output window automatically displays
the updated calibration date.
Check the calibrating values in the Value View tab AC operational values.
Carry out the calibration for the voltage measuring ranges AC 110 V, AC 230 V and AC 400 V in
accordance of the described work steps.