13 Technical Data
13.1 General Device Data
268 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Inputs for Alternating Current Measurements (Connector Block E)
Binary Outputs (Connector Block G)
Input alternating currents
Rated input current range 1 A
5 A
Max. input current 2 x rated input alternating current
Power consumption per input
at 1 A 4 mVA
at 5 A 100 mVA
Further information about the current measuring inputs
Max. rated input voltage 150 V
Measuring error (with calibration) at 23 °C ± 1 °C 50 Hz
or 60 Hz
Typically 0.1 % at reference conditions
Thermal stability 10 A continuous
100 A for max. 1 s
Maximum contact voltage
Alternating voltage 230 V
Direct voltage 250 V
Maximum currents
Maximum continuous contact current 100 mA
Maximum pulse current for 0.1 s 300 mA
Further information about the binary outputs
Internal impedance 35
Admissible switching frequency 10 Hz
Number of switching cycles Unlimited