14 Operational Indications
283SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
1) The SD card has no contact or is defective; you must not replace the card yourself. The device also works
without active SD card. However, data storage when operating the recorders is not possible. In this case,
the recorder data can be forwarded and processed only via communication.
Limit Violation x Indication that a parameterized lim-
iting value has been violated
Indication on: The limit of the monitored measured value
has been violated or no measured value is parameter-
ized as input of the limiting value.
Indication off: The limit of the monitored measured value
is not violated.
Message invalid: The monitored measured value is
invalid
(e.g. frequency at V < 15 % of V
rated
).
x = 1 to 16
Indication 1 from
Remote
Status of the indications that can be
set to control the LEDs and the
binary outputs via the communica-
tion.
Indication on: ON
Indication off: OFF
Message invalid: Not yet updated via the communication
or again invalid via the communication
Indication 2 from
Remote
Binary Output 1 Status of binary outputs ON/OFF Indication on: ON
Indication off: OFF
Only if not output as counter output
(for counter output = 0)
Binary Output 2
Reset Energy The energy counters were reset. Indication on: Energy counters reset
Rotating Field Clock-
wise
Indication of rotation voltage Indication ON: Phase sequence Va-Vb-Vc, rotation
clockwise
Indication OFF: Phase sequence Va-Vc-Vb, (2 phases
interchanged); rotation anti-clockwise
Indication invalid: Direction of rotation can not calculated
(e.g. no voltage applied)
Group indication x Up to 4 single-point indications can
be linked logically and combined to
a group indication.
A total of 4 group indications (x = 1 to 4) can be param-
eterized.
Supply Voltage Event
Available
Indication of a supply voltage event Overvoltage, undervoltage, frequency interruption
Frequency Event
Available
Indication of a frequency event Overfrequency or underfrequency
Volt. Unbalance
Event Available
Indication of a voltage unbalance
event
Voltage unbalance
PQ Event Indication of a fault recorder event A fault record was recorded.
SD Card Error Indication of an SD card error SD card defective or read/write error
1)
Indication Description Notes