15 Operating Parameters
15.2 Automation Functions
290 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
15.2 Automation Functions
The following automation functions are available:
• Limit violation 1-8
• Limit violation 9-16
• Group indication 1-4
15.2.1 Limit Violation 1-8 and 9-16
Parameter Default Setting Setting Range
Measurand -none- -none-
Va, Vb, Vc
Vab, Vbc, Vca
Ia, Ib, Ic
VN, Vavg
IN, Iavg
Pa, Pb, Pc, P
Qa, Qb, Qc, Q
Sa, Sb, Sc, S
cos (a), cos (b), cos (c), cos
PFa, PFb, PFc, PF
UIa, UIb, UIc, UI
f
Vunbal
Iunbal
THDS Va, THDS Vb, THDS Vc
THDS Ia, THDS Ib, THDS Ic
ab V, ca V
ab I, ca I
Q1a, Q1b, Q1c; Q1
Pinst (a-n), Pinst (b-n),Pinst (c-n)
Pst (a-n), Pst (b-n),Pst (c-n)
Plt (a-n), Plt (b-n),Plt (c-n)
Pinst (a-b), Pinst (b-c),Pinst (c-a)
Pst (a-b), Pst (b-c),Pst (c-a)
Plt (a-b), Plt (b-c),Plt (c-a)
(Setting ranges pending from network type
and device type)
Limit 0.00 -1 000 000 000 to 1 000 000 000 (unit)
Limit type Lower Lower
Upper
Hysteresis (%) 1.0 0.0 to 10.0
Violation indication Limit Violation x
(x = 1 to 16)
The name of the limiting value indication is
customizable.