EasyManua.ls Logo

Siemens Sicam P850 7KG85 Series - Display of Measurands; Measurands and Operational Measurement Uncertainty Acc. to IEC 62586-1 Product Standard, Class S, and Standards IEC 61000-4-30, Ed. 2 and IEC 61000-4-7 and IEC 61000-4-15

Siemens Sicam P850 7KG85 Series
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Measurands and Recording
4.3 Display of Measurands
65SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
4.3 Display of Measurands
4.3.1 Measurands and Operational Measurement Uncertainty acc. to IEC 62586-1
Product Standard, Class S, and Standards IEC 61000-4-30, Ed. 2 and
IEC 61000-4-7 and IEC 61000-4-15
Table 4-14 Measurands and their Operational Measurement Uncertainty
Measurands Unit Rated Value Measurement Range
Operat. Measurem.
Uncertainty acc. to
IEC 62586-1, Class S,
IEC 61000-4-30,
IEC 61000-4-7
IEC 61000-4-15
Voltage V
ph-ph
(delta)
Acc. to parameterization
VAC 110 V
AC 190 V
AC 400 V
AC 690 V
AC 600 V for UL
conditions
0 % to 120 % V
rated
±0.2 %
Voltage V
ph-N
(star)
Acc. to parameterization
V AC 63.5 V
AC 110 V
AC 230 V
AC 400 V
AC 347 V for UL
conditions
0 % to 120 % V
rated
±0.2 %
Voltage V
N
V AC 63.5 V
AC 110 V
AC 230 V
AC 400 V
AC 347 V for UL
conditions
0 % to 120 % V
rated
±0.2 %
Voltage unbalance U
2
% - 0 % to 100 % V
rated
±0.2 %
Frequency f Hz 50 Hz (±7.5 Hz)
60 Hz (±9 Hz)
42.5 Hz to 57.5 Hz
51.0 Hz to 69.0 Hz
50 mHz
(see Table 4-16)
Flicker Pst, Plt
(only SICAM P855)
- - Pst, Plt: 0,4 to 4
Pinst: 0 to 40
Acc. to class S,
IEC 61000-4-30:
Pst: ±10 %
Plt: ±10 %
Pinst: ±16 %
Harmonics of voltage
H_xV
ph
% or V - - Condition:
V
m
3% V
rated
Maximum error:
±5 % V
m
-------------------------------
Condition:
U
m
< 3 % V
rated
Maximum error:
±0.15 % V
rated

Table of Contents

Related product manuals