7.3.5.1 Event Recorders (Only SICAM P855)
Default Settings and Setting Ranges
Table 7-10 Event Recorders
Parameter Default Setting Setting Range
Supply voltage
Swell threshold 110 % 105 % to 140 % in 5-% steps
Dip threshold 90 % 75 % to 95 % in 5-% steps
Interruption threshold 5 % 1 %, 2 %, 3 %, 5 %, 8 % 10 %
Event hysteresis 2 % 1 % to 6 % in 1-% steps
Frequency
Underfrequency threshold 1 % 0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
Overfrequency threshold 1 % 0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
Unbalance
Voltage unbalance threshold 5 % 1 % to 5 % in 1-% steps