7 Operation at Use of a PC
7.3 Configuration of the Device
160 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
7.3.6.2 Communication Ethernet
Default Settings and Setting Ranges of the Communication Ethernet
Table 7-20 Communication Ethernet Settings
Parameter Default Setting Setting Range
IP address
1)
192.168.0.55 Any
0.0.0.0 = DHCP
Subnet mask
1)
255.255.255.0 Any
Default gateway
1)
192.168.0.1 Any
Enable SNMP no no
yes
OPC UA PubSub (MQTT) no no
yes
Bus protocol Modbus TCP IEC 61850
Modbus TCP
-none-
Bus Protocol Modbus TCP
Use a user-port number
2)
no no
yes
User-port number
2)
(can only be set when Use a user-port
number is parameterized with yes)
10000 10000 to 65535
Access rights for user port
(can only be set when Use a user-port
number is parameterized with yes)
Full Full
Read only
Access rights for port 502 Full Full
Read only
Keep Alive time 10 s 0 s = switch off
1 s to 65 535 s
Communication supervision time 600 * 100 ms 0 s = none
100 ms to 6 553 400 ms
Bus Protocol IEC 61850
IED name SICAM_P85x_01 max. 13 characters
Voltage - Dead band 0.2 % 0.2 %, 0.5 %, 1 % to 5 %, in
1-% steps
Current - Dead band 5 % 1 % to 5 %, in 1-% steps
Power - Dead band 0.5 % 0.5 %, 1 % to 5 %, in 1-%
steps
Power factor - Dead band 5 % 2 % to 5 %, in 1-% steps
Frequency - Dead band 0.05 % 0.02 %
0.05 %