7 Operation at Use of a PC
7.3 Configuration of the Device
167SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Default Settings and Setting Ranges of the Protocol OPC UA PubSub (MQTT)
Table 7-21 Protocol OPC UA PubSub (MQTT)
1)
After the parameter changes have been enabled, the device will reset.
In the Data transmission section, you can select whether the data groups are transmitted via the OPC UA
PubSub (MQTT) or not. Indications, operational measured values, flicker, security counters, and the asset
information files are always transmitted.
To change the settings of the protocol in the Configure tab, proceed as follows:
In the navigation window, select the Administratives menu and click Protocol OPC UA PubSub
(MQTT).
The Protocol OPC UA PubSub (MQTT) input/output window opens.
Parameter Default Setting Setting Range
Broker and network
Broker IP address or host name Empty
Any IP address or host name string
(maximum 128 characters)
Topic name /siemens/uapubsub/ Any (maximum 128 characters)
DNS server IP address 0.0.0.0 Any IP address
Data transmission
Harmonics voltage yes yes
no
1)
Harmonics current yes yes
no
1)
Energy counters yes yes
no
1)
Energy counters transmit cycle 1 min 1 min to 1440 min