7 Operation at Use of a PC
7.4 Value View and Evaluation
181SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
7.4.2.2 Records
Default Settings and Setting Options
Table 7-26 Value View and Evaluation - Records
Parameter Default Setting Setting Options
Record Type Measurement
recorder
Trend Recorder
1)
Measurement recorder
Measurement Recorder
Start time Current time Any with calendar function
Time format: depends on date/time
format config.
End time no setting, only display
Measurand source Frequency 10 s Frequency 10 s
Voltage
Current
Voltage angle
Current angle
Active power
Reactive power
Apparent power
Active power factor
Power factor
Phase angle
Frequency
Unbalance
THDS voltage
THDS current
Q1
Harmonic voltage magnitude
Harmonic current magnitude
Short term flicker (only SICAM P855)
Long term flicker (only SICAM P855)
Measurands f - 10 s The selectable Measurands depend
on the selected Measurand Source.
Aggregation Type
(The aggregation type is not displayed if
the frequency is 10 s, and flicker)
AVG AVG
MIN (not for harmonics)
MAX
Measurement output Table Diagram
Tabl e
CSV
Trend Recorder (only SICAM P855)
Query method
(only for trend recorder query)
By time By time
By event