7 Operation at Use of a PC
7.4 Value View and Evaluation
185SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
7.4.2.4 File Transfer
You can download the data from the SICAM P850/P855 in the standard format.
Trend records: PQDIF files
Measurements: PQDIF files and CSV files
Records for fault recorder: COMTRADE files
Default Settings and Setting Ranges
1)
In SICAM P850 Measurement recorder (CSV)
2)
Only SICAM P855
3)
Observe the information on how to download multiple files given in this chapter.
Table 7-28 File Transfer
Parameter Default Setting Setting Range
Start date Current date any
Calendar function
Time format: YYYY-MM-DD
End date Current date any
Calendar function
Time format: YYYY-MM-DD
Recorder type Trend recorder (PQDIF)
1)
Trend recorder (PQDIF)
2)
Measurement recorder (PQDIF)
2)
Measurement recorder (CSV)
Fault recorder (COMTRADE)
Download type Single file download Single file download
Multiple file download
3)
Recorder list -none- A file is generated as recording list in the
corresponding data format depending on the
parameterized data type and recorder type.

Table of Contents