7 Operation at Use of a PC
7.6 Example of a Parameterization and Measured Value Evaluation for SICAM P855
211SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
7.6.4 Performing the Measurement
Switch on the rated voltages and rated currents at the measuring inputs E and F of SICAM P855 observing
the safety notes given in Commissioning.
Read the measured values from the Value view and Evaluation tab by calling the Operational
parameters, Harmonics, AC power and energy, Binary outputs and Limits menu items according to
Value View and Evaluation in the navigation window.
The user interface displays the status of binary output G1/3 which corresponds to the parameterized
indication Vab_>11kV.
If the parameterized limit of the voltage Vab is exceeded, a corresponding limit violation indication is
displayed in the table.
Display the power quality events and the memory utilization on the Value view and Evaluation tab.
NOTE
Measured values and indications are refreshed after 5 s on the Value view and Evaluation tab.