10 Calibration
10.5 Calibrating the Phase Angle
250 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
10.5 Calibrating the Phase Angle
Measurement Setup
Figure 10-10 Measurement Setup for Phase Angle
Measuring Ranges
You can perform the calibration the phase angles for the following alternating voltage measuring ranges:
• AC 63.5 V
• AC 110 V
• AC 230 V
• AC 400 V
Settings the Phase Angles Reference Voltage to Reference Current
• Va to Ia = 0°
• Vb to Ib = 0°
• Vc to Ic = 0°
Calibration
To calibrate the phase angle, proceed as follows:
✧ Set up the measurement as shown in figure 10-10.
Reference
3
N
2
1
Voltage
Output
Reference
N
1
Current
Output
2
3
balanced balanced
NOTE
If you use a testing instrument of the type OMICRON as a reference, then you must connect the connection N
of the current output with the protective ground terminal of the SICAM P850/P855.