EasyManua.ls Logo

Siemens Sicam P855 7KG85 Series - Automation Functions

Siemens Sicam P855 7KG85 Series
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15 Operating Parameters
15.2 Automation Functions
290 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
15.2 Automation Functions
The following automation functions are available:
Limit violation 1-8
Limit violation 9-16
Group indication 1-4
15.2.1 Limit Violation 1-8 and 9-16
Parameter Default Setting Setting Range
Measurand -none- -none-
Va, Vb, Vc
Vab, Vbc, Vca
Ia, Ib, Ic
VN, Vavg
IN, Iavg
Pa, Pb, Pc, P
Qa, Qb, Qc, Q
Sa, Sb, Sc, S
cos (a), cos (b), cos (c), cos
PFa, PFb, PFc, PF
UIa, UIb, UIc, UI
f
Vunbal
Iunbal
THDS Va, THDS Vb, THDS Vc
THDS Ia, THDS Ib, THDS Ic
ab V, ca V
ab I, ca I
Q1a, Q1b, Q1c; Q1
Pinst (a-n), Pinst (b-n),Pinst (c-n)
Pst (a-n), Pst (b-n),Pst (c-n)
Plt (a-n), Plt (b-n),Plt (c-n)
Pinst (a-b), Pinst (b-c),Pinst (c-a)
Pst (a-b), Pst (b-c),Pst (c-a)
Plt (a-b), Plt (b-c),Plt (c-a)
(Setting ranges pending from network type
and device type)
Limit 0.00 -1 000 000 000 to 1 000 000 000 (unit)
Limit type Lower Lower
Upper
Hysteresis (%) 1.0 0.0 to 10.0
Violation indication Limit Violation x
(x = 1 to 16)
The name of the limiting value indication is
customizable.