15 Operating Parameters
15.4 Recording and Reporting
297SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
1)
The trend recorder also creates a PQDIF file when 1024 data points have been generated within the re-
cording interval.
Recorder of average - Min no no
yes
Recorder of average - Max no no
yes
Harmonics parity Odd Even
Odd
All
File generation every:
(corresponds to the setting of
the Average interval parame-
ter)
24 h File generation
every:
At average interval
1 h 30 s
2 h 1 min
2 h 10 min, 15 min,
30 min, 1 h or
2 h
4 h
6 h
12 h
24 h
Recorded file type PQDIF PQDIF
CSV
All
Flicker lamp model 230 V 230 V
120 V
Trend Recorder
Tolerance unit Percentage Percentage
Numerical
Tolerance number Percentage: 3 % of declared
input voltage Udin,
Numerical: 0.50 V
1% to 5% in 1 % steps
0.20 V to 500.0 V
Maximum recording interval 10 min 10 min, 30 min, 1 h, 2 h, 4 h, 6 h,
12 h, 24 h