6 Security
6.2 Account Management
101SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
✧ Create user accounts according to the following tables:
Table 6-4 Settings for Creating User Accounts
Settings Default Settings Description
User name Empty Up to 64 characters
New password 8 to 24 characters
Contains at least:
• 1 capital latin letter (A to Z)
• 1 small latin letter (a to z)
• 1 digital number (0 to 9)
• 1 special character from the set:
!, “, #, $, %, &, ‘, (, ), *, +, ,, -, ., /, :, ;, <, =,
>, ?, @, [, \, ], ^, _, ‘, {, }, ~.
Repeat new password
Roles
Click one or several option buttons to select a
role or several roles for a user account
according to Table 6-5.
Table 6-5 Overview of the Access Rights Assigned to Each Role
Description of the Access Rights Role
Guest
Viewer
Operator
Backup Operator
Engineer
Installer
Security Administrator
Security Auditor
User Account Manager
Administrator
General information viewing x
1)
xxxxxxxxx
Operation data viewing - x x x x x - - - x
Configuration settings viewing - xxxxx- - - x
Force values --x------x
Configuration downloading - - - x x x - - - x
Configuration change and uploading - - - - x x - - - x
Firmware change - - - - - x - - - x
RBAC management - - - - - - x - x x
Security management - - - - - - x - - x
Audit trail -------x-x