6 Security
6.3 Security Settings
106 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Configure the respective parameters according to the following table:
After the parameterization, click Confirm.
In the navigation window, select the Finish configuration menu and click Activation.
Table 6-8 Settings for the Security
Parameter Default Setting Setting Ranges
Maximum consecutive attempts 5 5 times to 12 times
Consecutive password attempt
time period
5 1 min to 10 min
Logon block timeout 30 30 min to 360 min
Session timeout 10
1 min to 1440 min (1 day)
If the device restarts, you must log on again.