7 Getting Started
7.2 Assembly
116 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
7.2.3 Assembly
To install the device into a switch panel, proceed as follows:
Push the device in installation position into the cut-out of the switch panel and hold the device tight.
Attach one of the supplied mounting elements each on both sides of the housing.
Figure 7-2 Stepwise Installation of the SICAM Q100 into a Switch Panel
Swing the mounting element (provided with the device) over the rear cone.
Move the mounting element to the position. Use a screw driver (0.6 mm x 4.5 mm) to fix the mounting
elements until the slipping clutch takes effect.
UL-Certification Conditions
Field Wires of Control Circuits shall be separated from other circuits with respect to the end-use requirements!
Mounting plate
Mounting element
1 mm (0.04 inch), steel
NOTE
The above mounting instructions must be performed correctly to provide sufficient protection against touching
live parts.