7 Getting Started
7.3 Electrical Connection
118 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
7.3.2 Electrical Connection of SICAM Q100
Figure 7-3 Terminal Connection of the Supply Voltage at the SICAM Q100
Terminal connection
of the supply voltage
DANGER
Hazard due to high voltage
Non-observance will lead to death or serious injury.
Work may only be carried out by trained personnel (see Preface) who are familiar with and observe the safety
requirements and precautions.
Work may never be carried out if there is any hazardous voltage present.
De-energize the device.
Isolating device: Connect a suitable isolating device upstream to de-energize the device. The isolating
device must be installed near the device, it must be easily accessible to the user and it must be marked
as an isolating device for the device.
Secure the supply voltage with an approved (UL/IEC) fuse: 1.6 A, type C.
If a melting fuse is used, a suitable approved (UL/IEC) fuse holder has to be used.
MAN_SICAM_Q100_US.book Page 118 Wednesday, June 5, 2019 9:31 AM