9 Operation at Use of a PC
9.3 Configuration of the Device
175SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.3.2 Automation Functions
9.3.3.2.1 Limit Settings
In the Select automation functions menu you can set upper or lower limits for up to 16 measured values. Limit
violations of the upper or lower value range can be output as indications. Limiting value violations can be
signaled at the device via the 2 binary outputs and the LEDs H1 and H2. Furthermore, all 16 limit violations can
be sent to peripheral devices via the communication interfaces.
The programmable limits are divided into two groups Limits 1-8 and Limits 9-16. The parameterization is
identical for all limits.
Default Settings and Setting Ranges of the Limits
1) 31 bytes of UTF-8
Table 9-6 Limit Settings
Parameter Default Setting Setting Range
Measurement -none- Acc. to list box
(see chapter 16)
Limit 0.0 -1 000 000 000 to 1 000 000 000 (unit)
Limit type Lower Lower
Upper
Hysteresis (%) 1.0 0.0 to 10.0
Violation indication Limit Violation x
(x = 1 to 16)
Any
Max. 31 characters
1)
MAN_SICAM_Q100_US.book Page 175 Wednesday, June 5, 2019 9:31 AM