9 Operation at Use of a PC
9.3 Configuration of the Device
179SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Parameterizing a Group Indication
To change, for example, group indication 1, proceed as follows:
In the navigation window, select the Operational parameters menu, then the Select automation
functions submenu and click Group indications 1-4.
Figure 9-37 Configure Tab, Group Indications Input/Output Window (Detail)
Select the desired parameters in the list boxes and option fields as described in Table 9-7.
After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
If you do not want to make any additional settings, continue with the Activation of the device configuration
according to section Activating the Set of Parameters. If you want to change other settings, enter the
changes and then enable the device configuration as described in section Activating the Set of
Parameters.
NOTE
Sources are assigned inside a group indication sequentially from source 1 to source 4.
If you select -none- at the 1st source in a group indication, you cannot configure further sources in this group
indication. In this case, the group indication is inactive.
You can also integrate group indications into subordinated group indications, for example group indication 1 in
group indication 3.