9 Operation at Use of a PC
9.3 Configuration of the Device
180 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.4 HMI
In the Configure tab, you can view and, if necessary, edit the display settings. You can select these parameters
in the HMI menu in the navigation window. The menu contains the following elements:
• Display settings
• User-defined screen
9.3.4.1 Display Settings
Default Settings and Setting Ranges
Parameterizing the Display Settings
To change the properties of the display, proceed as follows:
✧ In the navigation window, select the HMI menu and click LCD Property.
Figure 9-38 Configure Tab, Display Settings Input/Output Window
✧ Enter the desired values into the fields and select the corresponding parameters in the option fields as
described in Table 9-8.
✧ After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
Table 9-8 Display Settings
Parameter Default Setting Setting Range
Contrast 8 0 to 10
Time until dimmed 10 1 min to 99 min
Refresh time 1 000 330 ms to 3 000 ms
Inverse display no no
yes
Phase label (L1,L2,L3) (L1,L2,L3)
(a,b,c)