EasyManua.ls Logo

Siemens SICAM Q100 7KG95 Series - Page 197

Siemens SICAM Q100 7KG95 Series
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 Operation at Use of a PC
9.3 Configuration of the Device
197SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.6.3 Recorder Parameter
Default Settings and Setting Ranges
Table 9-16Recorder Parameter
Parameter Default Setting Setting Range
Measurement Recorder
PQ data Parameter
Average intervals - Frequency 10 s fixed
Short-term flicker 10 min fixed
Long-term flicker 2 h fixed
Average interval - Voltage,
Unbalance and Harmonics
10 min 30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
Record additional data (I, P, Q,
S etc.)
no no
yes
Recorder of average - Min no no
yes
Recorder of average - Max no no
yes
Harmonics parity Odd Even
Odd
All
File generation every:
1)
(corresponds to the setting of
the Average interval parame-
ter)
The created PQDIF files can be
downloaded via the user inter-
face or with the IEC 61850 pro-
tocol.
24 h At average interval File generation
every:
30 s 1 h (fix)
1 min 2 h (fix)
10 min, 15 min,
30 min, 1 h or
2 h
2 h
4 h
6 h
12 h
24 h
Recorded file type PQDIF PQDIF (see chapter 9.4.2.5)
CSV
All
Flicker lamp model 230 V 230 V
120 V
Energy value Parameter
Energy value recorder 10 minutes Not configurable
The same as the value of Interval set in
Configure -> Energy management ->
Energy freeze and reset.
Trend Recorder
MAN_SICAM_Q100_US.book Page 197 Wednesday, June 5, 2019 9:31 AM

Table of Contents

Related product manuals