9 Operation at Use of a PC
9.3 Configuration of the Device
198 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
1)
The interval of aggregated values of harmonics and interharmonics will always synchronize with the setting
of Average interval in Measurement recorder.
Parameterizing the Recorder Parameters
To change the Recorder management, proceed as follows:
✧ In the navigation window, select the Recording and Reporting menu and click Recorder management.
Figure 9-48 Configure Tab, Recorder Management Input/Output Window
✧ Select the desired parameters in the list boxes and option fields as described in Table 9-16.
✧ After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
Tolerance unit Percentage Percentage
Numerical
Tolerance number Percentage: 3 % of primary
nominal voltage,
Numerical: 0.5 V
1% to 5% in 1-% steps
0.2 V to 500.0 V
Maximum recording interval 10 min 10 min, 30 min,
1 h, 2 h, 4 h, 6 h, 12 h, 24 h
Table 9-16Recorder Parameter
NOTE
The voltage is recorded in the following connection types:
• 3P4W (3 phases/4 wires): phase-to-phase voltage or
phase-to-ground voltage
• 3P3W (3 phases/3 wires): only phase-to-phase voltage
MAN_SICAM_Q100_US.book Page 198 Wednesday, June 5, 2019 9:31 AM