9 Operation at Use of a PC
9.3 Configuration of the Device
205SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.6.5 Memory Management
Default Settings and Setting Ranges
1)
The memory sizes for event list, PQ records, fault records, and mains signaling voltage records can be
changed.
2)
The memory size for continuous recording is calculated automatically and forms the difference to 100 %
of the total memory size. The maximum total memory size of 100 % cannot be exceeded due to
parameterization errors.
3)
If the residual memory capacity falls below 31 %, activation is no longer possible. In this case, the Action
was not successful indication appears on the status bar.
Parameterizing the Memory Allocation
Table 9-19 Memory Management
Parameter Default Setting Setting Range
Memory splitting
Event recorder 1.0 % 1 % to 19 %
1)
Measurement recorder 35.0 %
(the recording time depends on
the aggregation interval)
33 % to 51 %
1)
Trend recorder 47.0 %
(residual storage capacity)
Min. 31 %
2) 3)
Fault recorder 3.0 %
(number of records depends on
the fault-record time)
3 % to 21 %
1)
Mains signaling voltage recorder 14 %
(number of records depends on
the record time of the mains sig-
naling voltage)
14 % to 20 %
1)
NOTE
If the device has been recording data for a longer period, a modification of the memory areas can lead to the
following indication:
Memory size should not be changed now. If you active changes, all PQ data will be lost. Please back up data
before activation or cancel changes.
This indication is issued only if the stored data and the expected data would exceed the memory capacity of
the SD card.