9 Operation at Use of a PC
9.3 Configuration of the Device
235SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.7.4 Communication Serial via RS485 Interface
Default Settings and Setting Ranges of the Communication Serial
Table 9-31 Communication Serial Settings
Parameter Default Setting Setting Range
Bus protocol Modbus RTU -none-
Modbus RTU
Modbus RTU Master
Bus Protocol Modbus RTU (Slave)
Device address 1 1 to 247
Baud rate 19 200 bit/s Acc. to list box
(see chapter 16)
Parity Even Acc. to list box
(see chapter 16)
Access rights Full Full
Read only
Communication supervision time 600 * 100 ms 0 s = none
100 ms to 6 553 400 ms
Bus Protocol Modbus RTU Master
Baud rate 19 200 bit/s Acc. to list box
(see chapter 16)
Parity Even Acc. to list box
(see chapter 16)