9 Operation at Use of a PC
9.3 Configuration of the Device
258 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Checking Additional Settings in the SICAM I/O Unit Subdevice
Binary Inputs
✧ Check the Threshold voltage and Software filter time settings of the binary inputs:
Figure 9-81 Binary Inputs of SICAM I/O Unit
✧ Check the time synchronization settings and select preferably Ethernet NTP as the source of time
synchronization, if available.
Communication indication
If data are exchanged correctly between SICAM Q100 and the SICAM I/O Unit, the indication I/O Mirror server
OK is set to ON in the SICAM I/O Unit.
MAN_SICAM_Q100_US.book Page 258 Wednesday, June 5, 2019 9:31 AM