9 Operation at Use of a PC
9.5 Maintenance
306 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Follow the notes in the following indication:
Figure 9-121 Firmware-Upload Indication When Loading a .cms File
After approximately 2 min, the device restarts automatically and the Log on tab appears for reconnection with
the device. The device firmware, default settings of parameters, text libraries, HTML files, or parts thereof are
uploaded.
You can find the firmware package in the download area in the Siemens Internet:
https://support.industry.siemens.com/cs/document/109743592/?en-US.
To upgrade the firmware to the latest version, select the following upload file:
File with extension .cms for upgrade from version V1.30 or later version to the latest version
If the firmware upload fails an error message is shown on the user interface. Following are some causes of
failure:
Invalid file extension
Invalid digital signature
Decoding failure
9.5.1.2 Abort Firmware Upload
If you do not want to update the firmware, click Abort in the section Abort firmware upload.
Follow the notes in the following indication:
Figure 9-122 Firmware-Upload Indication, Abort
NOTE
A file with extension .cms includes a digital signature that protects the integrity and authenticity of the
firmware package.
MAN_SICAM_Q100_US.book Page 306 Wednesday, June 5, 2019 9:31 AM