9 Operation at Use of a PC
9.5 Maintenance
315SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.5.4.3 Audit Log
The device provides an audit log to track the security-relevant events. The audit log can only be viewed by a
user assigned with the role of Security Auditor.
The Audit log is located in the Maintenance tab. To view the Audit log, proceed as follows:
In the navigation window, select the Message logs -> Audit log.
Audit messages are displayed on the HTML pages.
Figure 9-132 Maintenance Tab, Display Audit Log
To refresh the display of the audit log, click Audit log or press F5.
NOTE
The function Audit Log is only applicable to the SICAM Q100 firmware V2.00 and higher.
NOTE
The audit log is only available via HTML pages, not via the device display.
The audit log stores the latest 2048 audit messages. The older messages are automatically overwritten.
You cannot delete the audit messages manually.
For a new delivered device, audit logs created during production process are kept.