9 Operation at Use of a PC
9.5 Maintenance
318 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.5.5 Evaluation and Data Management – Transient Detection
To display and delete the transient events, proceed as follows:
In the navigation window, click the Value view and evaluation menu and the menu item Transient
detection.
Figure 9-133 Maintenance Tab, Delete Transient Events
Click Delete events in the input/output window.
All transient events in the input/output window are deleted without backup. The indication no. 0001
appears in the log list: Transient events deleted. The indication Action was successful appears in the
status bar.
NOTE
The last 255 transient events are displayed; older transient events are deleted automatically.
MAN_SICAM_Q100_US.book Page 318 Wednesday, June 5, 2019 9:31 AM