9 Operation at Use of a PC
9.7 Example of a Parameterization and Measured Value Evaluation
327SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.7 Example of a Parameterization and Measured Value Evaluation
9.7.1 Task Definition
Set the parameters via the Ethernet interface using the default IP address set upon delivery of the device.
Configure SICAM Q100 according to the topology.
Parameterize the indication of a limit violation for V
ab
> 11 kV with 10 % hysteresis and name the
indication.
Parameterize a binary output that is switched on for the duration of the limit violation.
Communicate via serial communication using device address 1, with a baud rate of 19.2 kbit/s, even
parity, full access rights, and a monitoring time of 1 min.
Parameterize the Ethernet communication according to the network configuration specified by the system
operator.
Assign any name and specify the time/date format as YYYY-MM-DD and the time in 24-hour format.
Parameterize the Measurement recorder with an averaging time of 2 hours and activate the averaging
recorders for minimum and maximum values. Record all voltage harmonics.
Allocate 50 % storage capacity to the Measurement recorder.
Take over the factory-set report configuration.
Activate the device configuration you have created as the active parameter set.
Perform measurements, acquire the limiting value indication and record the measured values as defined
in the task.
9.7.2 Initial Situation
Topology
4-wire system
Rated input voltage (ph-ph): AC 10 kV
Rated input current: AC 100 A
Rated frequency: 50 Hz
Connection: any load via transformers
Voltage transformer: 10 000 V : 100 V
Current transformer: 100 A : 1 A
Primary nominal voltage: 230.00 V
Communication via Ethernet and RS485 interfaces
Network Configuration
Default IP address: 192.168.0.55
User IP address: 192.168.1.40 (customer-specific)
Subnet mask: 255.255.255.0
Default gateway: 192.168.1.1