9 Operation at Use of a PC
9.7 Example of a Parameterization and Measured Value Evaluation
334 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Enable the active parameter set in the device as described in Activating the Set of Parameters.
9.7.4 Performing the Measurement
Switch on the rated voltages and rated currents at the measuring inputs E and F of SICAM Q100
observing the safety notes given in chapter 7.7.
Read the measured values from the Value view and Evaluation tab by calling the Operational
parameters, Harmonics, AC power and energy, Binary outputs and Limits menu items according to
chapter 9.4 in the navigation window.
The user interface displays the status of binary output G1/2 which corresponds to the parameterized
indication Vab_>11kV.
If the parameterized limit of the voltage Vab is exceeded, a corresponding limit violation indication is
displayed in the table.
Display the power quality events and the memory utilization on the Value view and Evaluation tab.
NOTE
After changing the network settings and subsequent parameter activation the device will reset.
NOTE
Measured values and indications are refreshed after 5 s on the Value view and Evaluation tab.