10 Operation at Use of the Display
10.4 Parameterization
349SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Submenu Display Number 80.3: Basic Parameters
Figure 10-21 Submenu Display Number 80.3, Basic Parameters
80.3
Basic
parameters
82.0
Voltage inputs
Enter
Edit
82.1
Current inputs
Enter
82.0
Connection type
Use PTs?
etc.
+
-
Enter
82.1
Current inputs
Use CTs?
82.2
Zero point sup .
EditEnter
82.2
Zero point sup .
Setting value
Edit
Select. parameters acc .
to following table
OkEsc
X or Y
X
Y
NOTE
The selection of the transformers only becomes active after a delay of 5 s.
Table 10-3 Basic Parameter Settings
Parameter Default Setting Setting Range
Voltage Inputs
Connection type 3P4W 1P2W (1-phase system)
3P3WB (three-wire, equal load)
3P3W_2I (three-wire, any load (2*I))
3P3W_3I (three-wire, any load (3*I))
3P4WB (four-wire, equal load)
3P4W (four-wire, any load)
Use PTs? No (no checkmark) Yes (checkmark)
No (no checkmark)
MAN_SICAM_Q100_US.book Page 349 Wednesday, June 5, 2019 9:31 AM