10 Operation at Use of the Display
10.4 Parameterization
356 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
1)
These values are necessary if no Modbus slave device has been configured for the requested Unit ID. If
a Modbus slave device was configured, its values are used.
Table 10-9 Modbus TCP/RTU Gateway Settings
Parameter Default Setting Setting Range
Activated no no
yes
Unit ID of this device 255 1 to 255
Retry limit
1)
2 0 to 10
Response timeout
1)
50 ms (1 to 6 000) * 10 ms
= 10 ms to 60 s
MAN_SICAM_Q100_US.book Page 356 Wednesday, June 5, 2019 9:31 AM