14 Technical Data
14.1 General Device Data
380 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
14.1 General Device Data
14.1.1 Power Supply
Direct Voltage
Alternating Voltage
Rated input voltages 24 V to 250 V
Admissible input voltage tolerance ±20 %
Permitted ripple of the input voltage 15 %
Maximum inrush current
At 110 V < 15 A
At 220 V to 300 V 22 A; after 250 µs: < 5 A
Maximum power consumption 6 W
Rated input voltages 110 V to 230 V
System frequency at AC 50 Hz/60 Hz
Admissible input voltage tolerance ±20 %
Permitted harmonics 2 kHz
Maximum inrush current
At 115 V < 15 A
At 230 V 22 A; after 250 µs: < 5 A
Maximum power consumption 16 VA
MAN_SICAM_Q100_US.book Page 380 Wednesday, June 5, 2019 9:31 AM