EasyManua.ls Logo

Siemens SICAM Q100 7KG95 Series - Test Data; Electrical Tests

Siemens SICAM Q100 7KG95 Series
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14 Technical Data
14.2 Test Data
387SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
14.2 Test Data
Reference Conditions according to IEC 62586-1 for Determining the Test Data
14.2.1 Electrical Tests
Standards
Insulation Test according to IEC EN 61010-1 and IEC EN 61010-2-030
Ambient temperature 23 °C ± 2 °C
Relative humidity 40 % to 60 % RH
Supply voltage V
PS
± 1 %
Phases (3-wire network) 3
External continuous magnetic fields DC field: 40 A/m
AC field: 3 A/m
DC components V/I none
Signal waveform sinus
Frequency 50 Hz ± 0.5 Hz
60 Hz ± 0.5 Hz
Voltage magnitude Udin ± 1 %
Flicker Pst < 0.1 %
Unbalance (all channels) 100 % ± 0.5 % of Udin
Harmonic 0 % to 3 % of Udin
Interharmonic 0 % to 0.5 % of Udin
Standards: IEC EN 61000-6-2
IEC EN 61000-6-4
IEC EN 61010-1
IEC EN 61010-2-030
Inputs/Outputs Insulation Rated
Voltage
ISO Test Voltage Category
Current measurement inputs Reinforced 150 V AC 2.3 kV Cat. III
Voltage measurement inputs Reinforced 600 V Surge voltage
9.76 kV
Cat. III
300 V Cat. IV
Supply voltage Reinforced 300 V DC 3.125 kV Cat. III
Binary outputs Reinforced 300 V AC 3.536 kV Cat. III
Binary inputs Reinforced 300 V AC 3.536 kV Cat. III
Ethernet interface SELV < 24 V AC 1500 V -
RS485 interface SELV < 24 V DC 700 V -
MAN_SICAM_Q100_US.book Page 387 Wednesday, June 5, 2019 9:31 AM

Table of Contents

Related product manuals