EasyManua.ls Logo

Siemens SICAM Q100 7KG95 Series - Page 388

Siemens SICAM Q100 7KG95 Series
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14 Technical Data
14.2 Test Data
388 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
EMC Tests for Immunity (Type Tests)
EMC Test for Noise Emission (Type Test)
Standards: IEC EN 61000-6-2
For more standards see also individual
functions
Electrostatic discharge, Class III,
IEC 61000-4-2
6 kV contact discharge; 8 kV air discharge,
both polarities; 150 pF; R
i
= 330
with connected Ethernet cable
High frequency electromagnetic field, amplitude-modulated,
Class III
IEC 61000-4-3
10 V/m; 80 MHz to 3 GHz; 80 % AM; 1 kHz
Fast transient bursts, Class III
IEC 61000-4-4
2 kV; 5 ns/50 ns; 5 kHz;
Burst length = 15 ms;
Repetition rate 300 ms;
Both polarities;
R
i
= 50 ;
Test duration 1 min
High energy surge voltages (SURGE), Installation Class III
IEC 61000-4-5
Impulse: 1.2 µs/50 µs
Auxiliary voltage Common mode: 2 kV; 12 ; 9 µF
Diff. mode:1 kV; 2 ; 18 µF
Measuring inputs, binary inputs, and
relay outputs
Common mode: 2 kV; 42 ; 0.5 µF
Diff. mode: 1 kV; 42 ; 0,5 µF
Line-conducted high frequencies, amplitude-modulated, Class
III
IEC 61000-4-6
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
Power system frequency magnetic field
IEC 61000-4-8, Class IV;
30 A/m continuous; 300 A/m for 3 s
1 MHz test, Class III, IEC 61000-4-18 2.5 kV (peak); 1 MHz; = 15 µs;
400 Surges per s;
Test duration 1 min; R
i
= 200
Standard: IEC EN 61000-6-4
Disturbance voltage to lines, only auxiliary voltage
IEC-CISPR 22
150 kHz to 30 MHz Limit Class A
Disturbance-field strength
IEC-CISPR 22
30 MHz to 1000 MHz Limit Class A
MAN_SICAM_Q100_US.book Page 388 Wednesday, June 5, 2019 9:31 AM

Table of Contents

Related product manuals