16 Operating Parameters
16.1 Process Connections
399SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
1)
Power quality values for and Calculate Voltage RMS values PN and PP are available only under Net-
work type is selected as Four-wire, three-phase, unbalanced.
2)
Transformer ratio In is available only if the following Network type is selected: Four-wire, three-phase,
unbalanced.
16.1.2 Binary Inputs U1/U2 and U3/U2
Parameter Default Settings Setting Range
Threshold voltage
Threshold voltage
(one setting for both binary inputs)
19 V 19 V
88 V
176 V
Binary inputs
Terminals U1/2
Routed as:
1)
Status information Status information
Load profile source
Tariff source
Software filter time
(only settable if Routed as: Status information
has been set)
1 (* 2 ms) 2 ms to 120 000 ms
(settable in 2-ms increments)
Source inverted no no
yes
Add entry to operational log
(only settable if Routed as: Status information
has been set)
yes no
yes
Binary input indication Binary Input 1 Any
Max. 31 characters
2)
Terminals U3/2
Routed as:
1)
Status information Status information
Load profile source
Tariff source
Software filter time
(only settable if Routed as: Status information
has been set)
1 (* 2 ms) 2 ms to 120 000 ms
(settable in 2-ms increments)
Source inverted no no
yes
Add entry to operational log
(only settable if Routed as: Status information
has been set)
yes no
yes
Binary input indication Binary Input 2 Any
Max. 31 characters
2)
MAN_SICAM_Q100_US.book Page 399 Wednesday, June 5, 2019 9:31 AM