16 Operating Parameters
16.1 Process Connections
402 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Operating mode Persistent Persistent
Persistent with fail safe
Pulse
Pulse with retrigger
Output time for pulse operating
mode (setting only possible if oper-
ating modes Pulse and Pulse with
retrigger)
20 (* 10 ms) 50 ms to 3 600 000 ms
Source Type Energy Counter
Energy counter -none- -none-
WPa_exp
WPb_exp
WPc_exp
WP_exp
WPa_imp
WPb_imp
WPc_imp
WP_imp
WQa_ind
WQb_ind
WQc_ind
WQ_ind
WQa_cap
WQb_cap
WQc_cap
WQ_cap
WSa
WSb
WSc
WS
WP_exp_tariff_x (x = 1 to 8)
WP_imp_tariff_x (x = 1 to 8)
WQ_ind_imp_tariff_x (x = 1 to 8)
WQ_cap_imp_tariff_x (x = 1 to 8)
WQ_ind_exp_tariff_x (x = 1 to 8)
WQ_cap_exp_tariff_x (x = 1 to 8)
WQ_ind_tariff_x (x = 1 to 8)
WQ_cap_tariff_x (x = 1 to 8)
WS_tariff_x (x = 1 to 8)
Energy increase per pulse 1.0 Wh 0.1 Wh/VAh/varh to
1 000 000 Wh/VAh/varh
Output time pulse operating mode 20 * 10 ms = 200 ms 50 ms to 3 600 000 ms
Parameter Default Settings Setting Range