16 Operating Parameters
16.3 HMI
407SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.3 HMI
16.3.1 Display Settings
16.3.2 User-Defined Screen
Parameter Default Setting Setting Range
Contrast 8 0 to 10
Time until dimmed 10 0 min to 99 min
Refresh time 1 000 330 ms to 3 000 ms
Inverse display no no
yes
Phase label (L1,L2,L3) (L1,L2,L3)
(a,b,c)
Parameter Default Setting Setting Range
Screen type -none- -none-
2 measured values, numerical
4 measured values, numerical
2 measured values, graphical + numerical
3 measured values, graphical + numerical
Screen name USER_SCREEN_x
(x = 1 to 4)
Max. 18 characters
Only English and German letters, num-
bers, and special characters are permitted.