EasyManua.ls Logo

Siemens SICAM Q100 7KG95 Series - Trigger Management

Siemens SICAM Q100 7KG95 Series
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 Operating Parameters
16.5 Recording and Reporting
413SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.5.2 Trigger Management
1)
The detection mode will always synchronize with the setting of Record ph-ph voltage.
Parameter Default Setting Setting Range
Voltage trigger limits
Trigger active no no
yes
Tolerance unit Percentage Percentage
Numerical
Lower threshold 90.00 %
of the nominal/declared
supply voltage
0.00 % to 99.99 % of the nominal/declared
supply voltage
0.0 V to 1 000 000.0 V
Upper threshold 110.00 %
of the nominal/declared
supply voltage
100.0 % to 10 000.0 % of the nominal/de-
clared supply voltage
0.0 V to 1 000 000.0 V
Hysteresis 2.00 %
of the nominal/declared
supply voltage
0.0 % to 50.0 % of the nominal/declared
supply voltage
Detection mode
1)
ph-N ph-N
ph-ph
Current trigger limits
Trigger active no no
yes
Tolerance unit Percentage Percentage
Numerical
Lower threshold 90.00 %
of nominal current In
0.00 % to 99.99 % of of nominal current In
0.0 A to 1 000 000.0 A
Upper threshold 110.00 %
of nominal current In
100.0 % to 10 000.0 % of of nominal
current In
0.0 A to 1 000 000 A
Hysteresis 2.00 %
of nominal current In
0.0 % to 50.0 % of of nominal current In
Configuration binary trigger
Trigger active no no
yes
Trigger source Binary Input 1 Indication 1 from Remote
Indication 2 from Remote
Binary Input 1
Binary Input 2
Trigger value OFF ON
OFF
Waveform capture setting
Total recording duration 2.0 s 0.2 s to 3.0 s in 0.2-s steps
Pretrigger ratio 10 % 0 % to 30 % in 5-% steps
Record ph-ph voltage no no
yes
MAN_SICAM_Q100_US.book Page 413 Wednesday, June 5, 2019 9:31 AM

Table of Contents

Related product manuals