16 Operating Parameters
16.5 Recording and Reporting
414 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.5.3 Recorder Parameters
Parameter Default Setting Setting Range
Measurement recorder
PQ data Parameter
Average intervals - Frequency 10 s fixed
Short-term flicker 10 min fixed
Long-term flicker 2 h fixed
Average interval - Voltage /
Unbalance / Harmonics
10 min 30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
Record additional data (I, P, Q,
S etc.)
no no
yes
Recorder of average - Min no no
yes
Recorder of average - Max no no
yes
Harmonics parity Odd Even
Odd
All
File generation every:
(corresponds to the setting of
the Average interval parame-
ter)
The created PQDIF files can be
downloaded via the user inter-
face or with the IEC 61850 pro-
tocol.
24 h At average interval File generation
every:
30 s 1 h (fix)
1 min 2 h (fix)
10 min, 15 min,
30 min, 1 h or
2 h
2 h
4 h
6 h
12 h
24 h
Recorded file type PQDIF PQDIF
CSV
All
Flicker lamp model 230 V 230 V
120 V
Energy value Parameter
Energy value recorder 10 minutes Not configurable
The same as the value of Interval set in
Configure -> Energy management ->
Energy freeze and reset.
Trend recorder
MAN_SICAM_Q100_US.book Page 414 Wednesday, June 5, 2019 9:31 AM